Guide · Specifications and drawings · 07 19 00

Check water repellent specifications against exterior elevations, wall types, and the sealant and test panel plan

UFGS Section 07 19 00 Water Repellents, a NAVFAC-prepared guide specification issued in August 2023 after a complete review and update, covers clear water repellent treatments applied to above-grade concrete, concrete masonry, and plaster. It specifies silanes at three solids levels, siloxanes, low- and high-solids acrylics, and VOC-complying products, with performance tests for absorption, vapor transmission, water penetration through masonry, chloride ion penetration, and accelerated weathering, then a sample test panel with a field hose test, environmental and safety limits, cure periods by substrate, sealant sequencing, examination, protection of glass and landscaping, spray or brush application, appearance, a whole-building field hose test, and a joint manufacturer and applicator warranty.

Start with the drawing note of the issued Section 07 19 00: confirm that the exterior elevations show where each type of water repellent goes and designate it by a code that matches a kept product paragraph. Then check that the substrates on the wall types are the above-grade concrete, concrete masonry, or plaster the section covers, that the Surfaces to Be Coated paragraph has been edited so it does not override the drawn locations, that the test panel is specified once in the right section, and that the sealant schedule and the repellent agree on which goes first.

Assemble the review package

Gather the exterior elevations with water repellent codes, the wall types and wall sections showing the substrate, cavity, and interior finish, the parapet, coping, sill, and window and door jamb details, the sealant schedule and joint details, the landscape plan near treated walls, the concrete, masonry, and plaster sections with their cure and cleaning requirements, any durability or chloride criteria for a marine or deicing exposure, and the issued Section 07 19 00 with Sections 07 92 00, 04 20 00, 01 33 00, and 01 57 19. Follow one wall from its elevation code to the wall type, the sealant joints in it, and the test panel before assuming the others match.

WBDG publishes UFGS 07 19 00: Water Repellents as a public guide-specification reference (accessed November 16, 2026). Use your project’s issued specification and amendments for the actual comparison; the guide specification does not automatically govern your project. The checklist below is an original suggested review workflow, not a reproduction of the UFGS requirements.

Eight checks to run against the issued set

Use one record per location or system. The CSV contains the same eight prompts plus fields for source revisions, observed evidence, the review owner, the decision, and closure references.

Eight specification-to-drawing checksSwipe or scroll sideways to read all columns.
CheckSources to compareQuestion to resolve
What the drawings must showDrawing note (show the location of each type of water repellent; designate by code) + delete note (delete types not required) + Surfaces to Be Coated (all exterior surfaces of the bracketed substrates, including parapet backs, wall tops, and returns at frames) + Covered Surfaces (the same list plus window sills) + exterior elevations and wall typesDoes every code on the elevations match one kept product paragraph, have the specifier deleted the unused types, and has the blanket coat-all-exterior-surfaces language in both Surfaces to Be Coated and Covered Surfaces been edited to point at the drawn locations, so the two lists and the elevations agree, including at sills, wall tops, and the backs of parapets?
Substrates the section coversOpening note (above-grade concrete, concrete masonry, and plaster) + bracketed substrates in Qualifications, the test panel, Surfaces to Be Coated, Examination, and Spray Application (concrete, concrete masonry or masonry, plaster) + acrylic note (concrete, exposed aggregate, stucco, masonry, or stone) + Examination (mortar joints tight and sound) + wall types and finish legendAre all treated walls above grade, with below-grade walls sent to the dampproofing or waterproofing section, do the brackets say concrete masonry or masonry consistently, and if the elevations call for treating clay brick, stone, or stucco, has the specifier confirmed a product and test basis for that substrate, since the acrylic note names substrates the scope note does not?
Product type, appearance, and exposureMaterials (clear, non-yellowing, deep-penetrating, non-staining, interlocking bond) + opening note (penetrant-type repellents; no graffiti resistance or gloss) + Silane, 20, 40, and 85 Percent Solids + Siloxanes + Low-Solids and High-Solids Acrylic (breathing coatings; note accepts wet sheen or darkening) + VOC-Complying Water Repellents (a certification listed as a type) + Environmental Protection (local air district or CARB bracket) + exposure criteriaDoes the elevation code point to a penetrating silane or siloxane or to an acrylic coating, and if an acrylic is kept, has the Materials paragraph been edited so it does not forbid the sheen and darkening the acrylic note accepts, does any wall need graffiti resistance that these products do not give, and does the VOC limit for the project’s air district allow the chosen solids level?
Test standards and performance criteriaPerformance Requirements (absorption by ASTM C140/C140M; vapor transmission by ASTM E96/E96M; ASTM E514/E514M; AASHTO T 259 and T 260; ASTM G154) + Silane criteria (absorption by ASTM C642 and E514/E514M; vapor transmission by ASTM D1653; absorption values reported under E514/E514M) + Siloxane criteria (ASTM E96/E96M) + no criteria for the acrylic types + chloride tests without an acceptance value + SD-06 Test ReportsHas the specifier chosen one absorption method and one vapor transmission method per substrate and aligned Performance Requirements with the criteria paragraphs, has a criterion been written for any kept acrylic type, and where chloride resistance matters for a marine or deicing exposure, does the section state what result the test reports must show?
Units and printed valuesSilane, 20 Percent Solids (inch-pound density range garbled and not matching the metric range) + all three silane paragraphs (specific gravity temperature in metric and inch-pound that does not convert) + Siloxanes (density and flash point) + product data submittalsHas the specifier corrected the 20 percent silane density so the metric and inch-pound ranges agree, and fixed the specific gravity reference temperature, so a reviewer comparing the product data can tell which value governs?
Test panel and field hose testSample Test Panel (standard of quality; Contracting Officer approval) and note (specify panels in Division 03, 04, or 09) + Preparation of Sample Test Panel (bracketed substrate; blank for the section; full-height expansion joint sealed with project materials) + Testing (treat the left side, then the right side; hose test “similar to AAMA 501.2”, titled for storefronts, curtain walls, and sloped glazing) + Field Testing (“Navy Hose Stream Field Test” not defined; recoat the entire building if moisture shows inside) + wall typesIs the panel specified in one section only, with the blank filled, does the panel procedure keep an untreated area to compare against, and for a wall with a drained cavity or an interior finish, has the specifier defined what “inside of the wall” means for the field test, and is recoating the whole building the intended remedy when a leak may come from a crack, joint, or flashing that a repellent cannot fix?
Cure, moisture, weather, and sequencingWeather and Substrate Conditions (no application on substrates cured less than a stated period; temperature, rain, and drying limits) + Moisture Condition (per the manufacturer) + Examination (a fixed wall moisture content limit; cracks repaired; form release and curing compounds removed) + Masonry, Plaster, and Concrete Surfaces (cure periods by substrate; masonry differs from the general condition) + Inspections (manufacturer’s representative approval) + concrete, masonry, and plaster sectionsHas the specifier reconciled the cure period in the weather paragraph with the longer masonry period, chosen whether the manufacturer’s moisture limit or the Examination value governs, and checked that the concrete section’s curing compound will not block penetration on walls scheduled for repellent?
Sealants, glazing, landscaping, and warrantySealants (repellent after sealants are installed and cured, unless adhesion and compatibility are tested) + Compatibility (confirm with each joint sealer; bracketed sealant-first or masking options) + Protection (glass, glazed and prefinished products, landscape materials) + Cleaning + Warranty (joint manufacturer and applicator; moisture penetration through structurally sound surfaces) + sealant schedule and Section 07 92 00Do the sealant schedule and Section 07 92 00 state the same order of work as the kept paragraphs, has a compatibility test been required if the repellent goes first, do the elevations and landscape plan show the glass, prefinished metal, and plantings that need protection, and does the warranty term suit the owner’s expectations for the wall type?

Worked example: a split-face masonry barracks with plaster accents and an acrylic code

Illustrative example: a barracks has split-face concrete masonry walls, plaster accent bands, and a clay brick base course. The elevations tag the masonry WR-1 and the plaster WR-2 and leave the brick untagged. The issued Section 07 19 00 keeps the 40 percent silane and the high-solids acrylic, keeps Surfaces to Be Coated unedited with every bracket, leaves the test panel blank, and keeps both sealant brackets. The sealant schedule puts sealant after the coatings, the masonry section uses a shorter cure than the repellent masonry paragraph, and the wall type shows a drained cavity behind the block.

Ask the architect to decide whether the brick base is treated and to tag it, and to confirm the drawn locations govern. Ask the specifier to edit Surfaces to Be Coated and Covered Surfaces to match the elevations, to fill the test panel blank or move the panel to the masonry section, to keep one sealant bracket that matches the sealant schedule, to edit Materials for the acrylic, to reconcile the cure periods, and to define the field test result for a cavity wall.

Avoid a false conflict

Section 07 19 00 covers clear repellent treatments on above-grade concrete, concrete masonry, and plaster. Masonry construction follows Section 04 20 00 and the masonry guide, stucco follows Section 09 24 23 and the stucco guide, sealants follow Section 07 92 00 and the joint sealant guide, below-grade protection follows the dampproofing and waterproofing sections and guides, and paints and elastomeric coatings follow the painting section, so check those before calling a requirement missing. Some of the section’s own wording needs resolving: the Materials paragraph rules out the sheen the acrylic types produce, the acrylic types have no criteria, the test methods in Performance Requirements differ from those in the criteria paragraphs, one density range and the specific gravity temperatures do not convert, the masonry cure periods disagree, the coat-all-surfaces paragraphs override the drawing note, the panel is placed both here and in other divisions, and the field test is not defined. Ask the specifier which wording the project intends before treating a difference as a design conflict.

When requirements disagree, follow the project’s document-control and clarification process. Do not assume that drawings always override specifications, or the reverse. Identify the exact sources and request an authorized decision.

Close the issue across the affected documents

Record the location or tag, drawing and specification references, issue dates, observed difference, and the decision needed. Assign an owner and keep the item open until the response identifies the governing requirement. Check the revised drawings and specification references together; a response email alone may leave the issued package inconsistent.

For the overall process, use the guide to drawing and specification conflicts. Mark an inapplicable checklist row with a reason, and distinguish a verified correction from a question that still needs design information.

Where Groundbook fits

Groundbook’s drawing and specification review helps investigate potential disagreements in the documents you supply. Include the relevant specification sections and drawing references, then verify the cited evidence with the responsible reviewers before acting on a finding.

Questions, answered

FAQs

What should a water repellent specification review compare?

Compare what the drawings must show, the substrates the section covers, the product type, appearance, and exposure, the test standards and performance criteria, units and printed values, the test panel and field hose test, cure, moisture, weather, and sequencing, and sealants, glazing, landscaping, and the warranty.

What must the drawings show under UFGS 07 19 00?

The drawing note of the current UFGS 07 19 00 Water Repellents on WBDG asks the drawings to show the location of each type of water repellent and to designate it by code. The section’s Surfaces to Be Coated paragraph also lists parapet backs, wall tops, and returns at frames, so edit it to match the drawn locations. UFGS numbers are DoD guide specification numbers, not universal MasterFormat titles, and your project’s issued specification governs.

Is a water repellent the same as waterproofing or dampproofing?

No. Section 07 19 00 covers clear treatments on above-grade walls that reduce water absorption while letting vapor pass. Below-grade walls follow the dampproofing or waterproofing sections, and leaks through cracks, joints, or flashing need those fixed, not more repellent. Check that the wall types send each surface to the right section.

Can Groundbook check exterior elevations against Section 07 19 00?

Groundbook compares the drawing set with the specification sections and reference documents you upload, such as your issued Section 07 19 00, Sections 07 92 00 and 04 20 00, the wall types, and licensed standards you hold, and returns potential conflicts with links to the source pages. It has no built-in code library and does not select products, run or interpret absorption or hose tests, certify compliance, or approve test panels or submittals. Each finding is a question for the architect, the envelope consultant, the specifier, or the contracting officer.

Keep exploring

Continue your review

Check masonry specifications against wall details

Compare masonry unit types, reinforcement, grout, flashing, joints, and support details with the issued specification. Includes an editable checklist.

Explore

Check cement stucco specifications against exterior elevations, wall sections, and details

Compare stucco lath, framing, weather barrier, control joints, accessories, terminations at openings and grade, soffits, and finish coats with UFGS 09 24 23.

Explore

Check joint sealant specifications against drawings

Compare joint sealant type, joint design, substrate compatibility, and movement capability across wall details and specifications. Editable CSV included.

Explore

Check concrete specifications against drawings

Compare concrete mix references, slab finishes, joints, embeds, and curing requirements across specifications and drawings. Includes an editable checklist.

Explore

Check architectural concrete specifications against elevations, form joint layouts, finish legends, and sample panels

Compare exposed concrete finishes, form liners and ties, sample panels, galvanized reinforcing, cleaning, and sealer extent with UFGS 03 33 00.

Explore

Check bituminous dampproofing specifications against foundation, retaining, and cavity wall details

Compare dampproofing extent, groundwater basis, asphalt or coal-tar pitch, hot or cold method, primer, cavity walls, and curing with UFGS 07 11 13.

Explore

Check waterproofing specifications against details

Trace fluid-applied waterproofing from specification to substrates, joints, drains, and terminations. Includes a coordination checklist and editable CSV.

Explore

Check marine concrete specifications against pier, pile cap, and seawall drawings and the service life basis

Compare service life inputs, exposure zones, cover, reinforcement and coatings, strength basis, joints, and curing with UFGS 03 31 29.

Explore

Check air barrier specifications against drawings

Compare air barrier continuity, transitions, penetrations, and testing requirements across wall sections and specifications. Editable checklist included.

Explore

Connect masonry design notes, details and specifications

Check masonry drawings against their stated TMS 402 design and TMS 602 specification basis. Trace materials, reinforcement and interfaces with a CSV.

Explore

UFC 3-101-01 Architecture document review for DoD projects

Review DoD architectural sets against the reissued UFC 3-101-01: IBC modifications, air barriers, envelope renovation, mockups, and acoustics.

Explore

Drawings vs. specifications

Compare drawing requirements with specifications, schedules, and controls. Find potential equipment, material, and scope inconsistencies with Groundbook AI.

Explore

Bring your next set into focus

Set up a review or talk through your project with our team.

Check which walls your water repellent spec really covers

Trusted by hundreds of professionals