Check engineered wood beams by confirming that every beam drawn on the supplier layouts, architectural plans and sections is also sized on the structural framing plan, with its product, plies and grade. Then check each beam’s bearing, the post and footing below each end, the hangers where it carries or hangs from other members, the fastening of multi-ply beams, and the product’s suitability for exposed locations.
Find the beams no one sized
Engineered wood beams appear on several documents: the structural framing plan, the truss or joist supplier’s layout, the architectural sections and the ceiling plans. A beam that appears on one of them and not on the structural plan has no engineered size, grade or support.
In the house floor truss submittal load path review, the truss layout called for two long multi-ply LVL beams, one carrying the hung end of a girder and one carrying five trusses. The structural floor plan showed neither. In the same set, a long beam over an open patio carried ceiling joists from both sides with no size label, although every other beam on the sheet had one.
Twelve questions for engineered wood beams
Work through the beams one at a time, starting with those that carry other beams or girders. The CSV has columns for the location, the source references, the reviewer, the status, the decision and the closure evidence. It contains no design values; sizes and capacities come from the engineer of record, the supplier’s design and the manufacturer’s published data.
| Review area | Open these sources together | Question to resolve |
|---|---|---|
| Every beam on the structural plan | Structural framing plans, supplier beam and truss layouts, architectural plans | Is each beam the supplier layout, architectural plans or sections show also drawn and sized on the structural framing plan? |
| Size, plies and product | Beam callouts, beam schedule, structural notes | Does each callout give depth, width or number of plies, and the product type, with no beam drawn without a size? |
| Grade or stress class | Structural notes, beam schedule, specifications | Do the notes or schedule give one grade or stress class for each engineered wood product, matching the specification? |
| Multi-ply fastening | Beam details, structural notes, manufacturer requirements cited | Is the nailing, screwing or bolting that joins multi-ply beams shown, including side-loaded beams that carry joists or trusses from one side? |
| Bearing length and support | Beam ends on the framing plan, post schedule, bearing details | Is the bearing at each beam end shown, with a post, stud pack or wall sized for the reaction? |
| Posts and footings below | Framing plans, post schedule, foundation plan | Does a post or column continue from each beam end to a footing the foundation plan shows? |
| Beam-to-beam and girder connections | Framing plans, hanger schedule, connection details | Where a beam or girder hangs from another beam, is the hanger or connection named with its capacity and fasteners? |
| Loads the beam was sized for | Beam calculations, structural notes, truss and joist reactions | Do the beam calculations use the same wall, floor and roof loads and the same truss or joist reactions as the drawings? |
| Exposure and moisture | Architectural plans and sections, beam schedule, specifications | For beams at porches, patios, decks or other exposed locations, do the drawings state a product and treatment suited to that exposure? |
| Holes, notches and drops | Mechanical and plumbing plans, sections, beam details | Do any ducts, drains or recessed fixtures pass through or notch a beam, and do the drawings show it as allowed? |
| Flush and dropped beams in the ceilings | Sections, reflected ceiling plans, framing plans | Do the sections and ceiling plans show each beam flush or dropped as the framing plan assumes, at the depth drawn? |
| Who designs which beam | General notes, specifications, delegated design and submittal requirements | Do the notes say which beams the engineer of record sizes and which the supplier designs, and who reviews the supplier’s sizing? |
Mark a row not applicable only after recording why. A single-span header still needs its bearing and post checked.
Follow each beam end down
An engineered beam concentrates load at its ends. Check that each end has a post, stud pack or wall sized for its reaction, and that the post continues to a footing. The structural load path checklist follows those reactions through every floor. Where one beam hangs from another, the hanger is part of the design: the hanger and connector schedule checklist covers how to check it.
Compare the beams with the specification
The specification may limit the products, grades and treatments allowed. Read the engineered wood and glulam paragraphs of the rough carpentry section against the beam schedule. The rough carpentry specifications versus drawings guide found one federal guide specification requiring laminated strand and veneer products inside its glulam paragraph, which is the kind of conflict to settle before ordering. The AWC NDS guide covers the design standard for the members themselves.
Where Groundbook fits
Groundbook compares the structural framing plans, supplier beam and truss layouts, architectural plans and sections, specifications and calculations you upload, and returns potential conflicts with links to each source, such as a beam on a truss layout that has no size on the structural plan. It does not size beams, check their capacity or choose products. Each finding is a question for the engineer of record and the supplier. See cross-discipline coordination review for the workflow.