Start with the drawing note of the issued Section 03 45 00: confirm that the elevations and details show every unit with dimensions and reinforcement, the joints with sealant or gasket shape and size, the anchorage to the building frame with the loads it must carry, the reglets and inserts, each surface finish with its transitions, and the integral colors. Then check that one finish paragraph governs each exposed surface, that the samples, full-size panel, and mockup are kept or deleted on purpose, that the joint widths and envelope tie-ins are drawn because the section gives none, and that the design responsibility for connections is clear.
Assemble the review package
Gather the exterior elevations with the precast panel layout and finish legend, the wall sections and plan details at panel joints, corners, openings, parapets, and the base, the structural framing plans and slab and spandrel edge details with embeds or support steel at each floor and the roof, the structural general notes with design loads and the delegated design list, the joint sealant schedule, the air barrier, insulation, and flashing details, the site plan for a sample and mockup location, any site furnishing or paving plans with precast bollards, benches, or pavers, and the issued Section 03 45 00 with Sections 07 92 00, 03 30 00, the structural steel section, and the flashing and air barrier sections. Follow one panel from its elevation mark to its finish, joints, connections, and supporting member before assuming the others match.
WBDG publishes UFGS 03 45 00: Precast Architectural Concrete as a public guide-specification reference (accessed November 16, 2026). Use your project’s issued specification and amendments for the actual comparison; the guide specification does not automatically govern your project. The checklist below is an original suggested review workflow, not a reproduction of the UFGS requirements.
Eight checks to run against the issued set
Use one record per location or system. The CSV contains the same eight prompts plus fields for source revisions, observed evidence, the review owner, the decision, and closure references.
| Check | Sources to compare | Question to resolve |
|---|---|---|
| What the drawings must show | Drawing note (a complete design; location and details of units with all dimensions and reinforcement; joint details with sealant or gasket shape, dimensions, and location; anchorage devices to the building frame and connections of other materials, with gravity, live, and dynamic loads; reglet and insert locations; location of each surface finish with details of transitions; integral colors) + wood nailer, reglet, anchorage device, and gasket notes (locations and cross sections must be indicated) + elevations, wall sections, and details | Do the elevations key every panel and unit with a mark, finish, and color, do the details show each joint type with its sealant or gasket shape and size, do the connection details show anchorage types and the loads the manufacturer needs, and are reglets, nailers, and inserts located on the drawings rather than left to the shop drawings? |
| Design responsibility, loads, and connections | Standards and Loads (ASCE 7-16, ACI 318, PCI MNL-122; design loads on the drawings; differential temperature bracket whose default Fahrenheit value does not match its default Celsius value or the note) + Connections (type and configuration indicated; Contractor designs and sizes all connections) + Design Calculations (members, connections, and embedments not shown; sealed by a registered engineer; lifting) + Thermal Calculations (ASHRAE 90.1; connector spacing and solid concrete area) + structural general notes and delegated design list | Do the structural notes give the wind, seismic, and gravity loads the panels and connections must carry, is the delegated connection design listed with what the engineer of record will review, has the specifier entered the temperature differential in one consistent unit pair, and does the load standard edition match the one the project’s governing criteria adopt? |
| Finishes, colors, and transitions | Smooth, Exposed-to-View Surfaces (all exposed surfaces unless otherwise indicated) + Exposed Aggregate Finish (all exposed surfaces, including chamfers and returns, unless otherwise indicated) + Finishing for Formed Surfaces brackets (exposed aggregate by sanding and acid wash, abrasive blast, acid etch, honed, polished) and note + Exposed-to-View Facing Mixture bracket (white, gray, or buff cement) + Exposed Aggregate and fine aggregate paragraphs + Coloring Admixture bracket + finish legend and elevations | Has the specifier kept one default finish and named every other finish by location, so the smooth and exposed aggregate paragraphs do not both claim all exposed surfaces, does each finish on the elevations match a kept bracket and its method, are transitions between finishes detailed at reveals, and do the drawings or the section name the aggregate and integral color the finish depends on? |
| Samples, full-size panel, and mockup | Concrete Wall Panel Surface Finish Sample (small finish sample, then one full-size sample wall panel, unbracketed) + SD-04 (Full Size Sample Wall Panel bracketed; Form Liner; Brick Color Chips; Mock-up) + Mock-Up (anchors, connections, flashing, and joint fillers; water repellent applied and water-tested; job mock-up panel with edge, reveal, and brick coursing as shown; transported to the site and erected where directed) + Pre-Installation Meeting (water repellent applicator bracket) + sample display note + site plan | Has the specifier decided whether a full-size sample panel is required and made the submittal list agree, is a water repellent specified somewhere if the mockup is to be treated and water-tested, since this section specifies none, does the mockup include the joint, flashing, and connection actually detailed on the drawings, and does the site plan or the section say where the mockup stands? |
| Panel joints, gaskets, sealants, and the envelope | Joints (widths as specified unless otherwise indicated; the section specifies none) + Joint Sealing (Section 07 92 00) + Joint Materials (premolded closed-cell chloroprene gasket to the cross section indicated; brittleness temperature printed in metric and inch-pound values that do not agree) + Joints and Gaskets (continuous, compressed) + Flashing Reglets (stainless unbracketed, copper and galvanized brackets; note against galvanized at sea coasts and for staining) + Insulated Panel Accessories + wall sections, joint details, sealant schedule, and air barrier details | Are joint widths dimensioned on the details, is each joint drawn as a sealant joint, a gasket, or both, with the gasket cross section shown, do the sealant schedule and Section 07 92 00 cover the precast joints, does the air barrier and insulation line run continuously across panel joints and openings, and has one reglet metal been kept that suits the exposure? |
| Embedded items, anchorage, and connections to the frame | Plates, Angles, Anchors and Embedment + Inserts (threaded, wedge, and slotted; galvanizing brackets; the threaded insert paragraph allows cast steel and then requires malleable iron) + Wood Nailer Inserts (location and size must be indicated; AWPA use category) + Built-In Anchorage Devices note + Connection Devices (clip angles, clamps, fasteners) + Building Framing System (supporting members and embeds provided before placement) + Erection (welding to AWS D1.1, zinc-rich touch-up, grout as shown) + Welded Connection Visual Inspection + structural framing plans and edge details | Do the framing plans and spandrel or slab edge details show the embeds, angles, or support steel each panel bears and ties to at every floor and the roof, is it clear which trade furnishes and sets embeds in the steel or cast-in-place frame, do the connection details allow for the erection tolerances, and has the specifier fixed the threaded insert material sentence? |
| Plant and erector categories, thin brick, and other units | Fabricator Quality Certifications (PCI Group A category bracket AT, AD, AC, AB, or AA, or APA or NPCA) and category note + Erector Certification (PCI category A or S2) and Erector Qualifications bracket + opening note (wall panels, mullions, bollards, urns, railings, sills, copings, benches, planters, pavers) + Thin Brick Veneer (properties, face size bracket, color chips, form liner and bond breaker samples) + Sand-Cement Mortar and Pointing Grout notes + Precast Drawings bracket (brick joints and coursing aligned across panel joints) + elevations and site plans | Does the PCI category chosen match the most demanding units drawn, such as multiple mixes, returns, or tight tolerances, rather than only site furnishings, is the erector category right for load-bearing or non-load-bearing units, and where thin brick is drawn, do the elevations set the brick size and show coursing that aligns across panel joints, with one joint-filling method kept? |
| Strength, tolerances, acceptance, and the section’s own wording | Quality Control Testing During Fabrication (three specimens of each set tested at 28 days) versus the evaluation paragraph (averages two) + Concrete Strength at Time of Precast Unit Installation (two paragraphs printed, note says delete one) + Tolerances (PCI MNL-117 unless otherwise specified by “the Architect”) versus Modification of References (Architect/Engineer means the Contracting Officer) + defect limits that differ among Repair of Surface Defects, Finishing for Formed Surfaces, and Rejection + bearing pads citing AASHTO LRFD and MIL-C-882E (not in References) + fly ash note (no Class C) versus the blended cement bracket (Class C pozzolan) | Has the specifier made the strength evaluation match the testing table, kept one installation-strength paragraph, said who may set tighter tolerances, and set one defect limit for exposed surfaces that matches the approved sample, and do the elevations or notes call out any tighter tolerances or viewing distances the design relies on? |
Worked example: two panel finishes, thin brick, and connections nobody drew
Illustrative example: a three-story administration building is clad in architectural precast panels with an acid-etched field, smooth bands at each floor line, thin brick at the base, and precast copings and sills. The issued Section 03 45 00 keeps both the smooth and the exposed aggregate paragraphs with “unless otherwise indicated”, keeps the acid-etched and abrasive-blast brackets, requires a full-size sample panel while the submittal list brackets it, and keeps the water repellent steps in the mockup. The elevations hatch the two finishes without a transition detail, the joint details show a two-stage sealant joint with no dimension, and the steel framing plans show no embeds or support angles at the spandrel beams.
Ask the architect to add a finish legend that names the acid-etched and smooth finishes by location, to detail the transition reveal, to dimension the panel joints, and to show the air barrier tie-in at each joint. Ask the specifier to keep one default finish paragraph, to delete the unused finish brackets, to make the full-size sample and the submittal list agree, and to specify or delete the water repellent. Ask the structural engineer to give the panel design loads and to show the support steel and embeds at the spandrels, and to confirm which connections the precast engineer designs.
Avoid a false conflict
Section 03 45 00 covers plant-cast architectural units. Precast structural framing follows Section 03 45 33 or 03 41 33 and their guides, cast-in-place architectural concrete follows Section 03 33 00 and its guide, tilt-up panels follow their own section, joint sealants follow Section 07 92 00, flashing, air barriers, and insulation follow their own sections and guides, and the support frame follows the structural steel or concrete sections, so check those before calling a requirement missing. Some of the section’s own wording needs resolving: the temperature differential brackets do not convert, the strength evaluation and testing table count different specimens, the full-size sample and the submittal list disagree, the mockup treats with a water repellent the section never specifies, two finish paragraphs each claim all exposed surfaces, three paragraphs set different defect limits, the gasket brittleness values do not agree, joint widths are “as specified” with none specified, both installation-strength paragraphs print, the threaded insert material is stated two ways, and the bearing pad paragraph cites documents not in References. Ask the specifier which wording the project intends before treating a difference as a design conflict.
When requirements disagree, follow the project’s document-control and clarification process. Do not assume that drawings always override specifications, or the reverse. Identify the exact sources and request an authorized decision.
Close the issue across the affected documents
Record the location or tag, drawing and specification references, issue dates, observed difference, and the decision needed. Assign an owner and keep the item open until the response identifies the governing requirement. Check the revised drawings and specification references together; a response email alone may leave the issued package inconsistent.
For the overall process, use the guide to drawing and specification conflicts. Mark an inapplicable checklist row with a reason, and distinguish a verified correction from a question that still needs design information.
Where Groundbook fits
Groundbook’s drawing and specification review helps investigate potential disagreements in the documents you supply. Include the relevant specification sections and drawing references, then verify the cited evidence with the responsible reviewers before acting on a finding.