Guide · Specifications and drawings · 07 18 16

Check PMMA liquid-applied roofing specifications against roof plans, recover details, and traffic areas

UFGS Section 07 18 16 Cold Liquid-Applied Reinforced Polymethyl Methacrylate Roofing, a new NAVFAC-prepared guide specification issued in August 2025, covers a polymethyl methacrylate (PMMA) resin membrane reinforced with polyester fleece, applied over existing or new roofing in accordance with UFC 3-110-03, with its flashing membrane, primers, a resin-mortar wearing layer, and traffic surfacing. Its opening note presents it as a way to extend the service life of an existing roof instead of removing and replacing it, lists built-up, metal, single-ply, and modified bitumen roofing as acceptable existing substrates, and warns that the existing roof and its substrate must be structurally sound, properly attached, and dry. Its articles cover qualifications, product approvals, wind uplift, a contractor’s field survey with a moisture survey, weather limits, warranties, cool roofs, substrate preparation for each material, crack repair, flashings and penetrations, continuity testing, traffic surfacing and striping, and the manufacturer’s inspections.

Start with the existing roof: confirm that a moisture survey shows where the membrane and insulation are wet and that the drawings show what is removed and replaced before PMMA goes on, since the issued Section 07 18 16 applies PMMA only after those repairs are accepted and its opening note requires the existing roof to be sound, attached, and dry. Then check that the substrate of each roof area, the cover board and wind uplift basis, the approval listing, flashing heights at curbs and walls, drains, penetrations, expansion joints, traffic areas, continuity testing, and the warranty scope agree with the roof plan, the details, and the related sections.

Assemble the review package

Gather the roof plans with the existing roof system named for each area, the roof condition and moisture survey with core results and the drawing of wet areas, the removal and replacement plan for wet membrane and insulation, the tapered insulation and drainage plan with drains, overflows, and scuppers, the parapet, curb, wall, edge, scupper, drain, expansion joint, and through-wall flashing details, the mechanical, plumbing, and electrical roof plans with equipment, curbs, hot pipes, kitchen exhaust, grease discharge, and conduit penetrations, the structural drawings with deck type and the capacity of the existing roof, the plans of any pedestrian or vehicle deck with its traffic areas and striping, the wind design basis and uplift zones, the energy analysis and cool roof decision, the fall protection anchorages, the manufacturer’s details and approval listing, and the issued Section 07 18 16 with Sections 07 22 00, 07 60 00, 06 10 00, 07 92 00, 01 45 00, 01 33 29, and Section 07 55 00 where PMMA is the membrane under a protected membrane roof. Follow one roof area from its moisture survey to its finished surface, and one rooftop unit from its curb to its flashing, before assuming the others match.

WBDG publishes UFGS 07 18 16: Cold Liquid-Applied Reinforced Polymethyl Methacrylate Roofing as a public guide-specification reference (accessed November 10, 2026). Use your project’s issued specification and amendments for the actual comparison; the guide specification does not automatically govern your project. The checklist below is an original suggested review workflow, not a reproduction of the UFGS requirements.

Eight checks to run against the issued set

Use one record per location or system. The CSV contains the same eight prompts plus fields for source revisions, observed evidence, the review owner, the decision, and closure references.

Eight specification-to-drawing checksSwipe or scroll sideways to read all columns.
CheckSources to compareQuestion to resolve
Existing roof, moisture survey, and removalsOpening note (existing roof and substrate structurally sound, properly attached, and dry; acceptable existing substrates built-up, metal, single-ply, and modified bitumen) + System Description bracket (over existing, new, or concrete and the listed roof systems; PMMA only after deteriorated and wet membrane and insulation are removed and the roof is accepted; repairs to NRCA C3701) + Field Inspection and Existing Conditions Report (contractor’s field survey with a moisture survey and a drawing of entrapped moisture; SD-06) + roof survey + roof plansDoes a moisture survey from the design phase exist, and do the drawings show which wet membrane and insulation are removed and what fills each area, or is all of it left to the contractor’s survey after award, which the note describes as confirming conditions already shown in the design documents? Is the existing system of each roof area named on the roof plan and within the substrates the opening note accepts, and since the System Description bracket also offers concrete, which the note’s list omits, has the specifier said which surfaces each area presents?
Cover board, single-ply recover, and wind upliftCover Board note (some systems need the existing single-ply removed or cut before a cover board or new insulation; delete cover board and joint tape if not needed) + Cover Board Installation bracket (mechanically fastened or adhered, resisting uplift at corners, perimeter, and field) + Wind Uplift Resistance notes and bracket (include over a newly adhered cover board; ASCE 7-22 loads validated by FM testing; remove the FM reference over an unrated assembly; show calculated values in the specification or drawings) + SD-05 Wind Uplift Calculations + roof plan zones + structural drawingsWhere the existing roof is single-ply, has the manufacturer’s requirement to remove, cut, or overlay it been settled and drawn, where a cover board is added, is the Wind Uplift Resistance paragraph kept with the calculated uplift pressures shown by zone on the drawings or in the specification, as its note asks, where the existing assembly is unrated, has the FM test reference been removed, as the note directs, and does the cover board attachment kept in Cover Board Installation match the assembly those calculations assume?
Approval listing, fire classification, and qualificationsProduct Standards (FM Class I-4470 roofing system or roof coating system listing over existing roof substrates; tailoring note for Army and Navy) + Polymethyl Methacrylate Membrane article (“Systems meeting UL Class and FM 4470 Approval”) + References article (no FM, UL, or ICRI entry) + Manufacturer, Installer, and Inspector Qualifications (SD-07) + Quality Control note (roof consultant, engineer, or architect on the design team for larger or mission-critical roofs)Has the tailoring option been chosen so a single FM listing remains, does that listing cover the existing substrate actually present, has a fire classification been named with its UL test standard, since the membrane article says “UL Class” without naming a class or a standard, and have FM 4470 and that standard been added to the References article, which lists neither? Where the roof is large or mission critical, is a qualified roof consultant, engineer, or architect named on the design team, as the Quality Control note requires?
Substrate preparation, moisture, and primers by materialConcrete Substrates (ACI 301 and ACI SPEC 308.1, relative humidity by ASTM F2170, ICRI concrete surface profile, adhesion by ASTM D4541) + Masonry Substrates (sound walls; ASTM F2170 or F2659) + Metal Substrates (“near-white metal in accordance with SSPC SP 15 (Commercial grade power tool cleaning)”; galvanized passivation removal) + Rigid Plastics + Primers article and moisture mitigation primer note + Primer, Low Odor Epoxy, and Moisture Mitigation Epoxy Primer Application + roof details and existing conditionsDo the details and the existing conditions record say which material each surface presents, existing membrane, concrete deck, masonry parapet, galvanized curb, or plastic pipe, so the matching preparation, primer, and adhesion test apply, is the moisture mitigation primer kept or deleted to follow the moisture test results, as its note directs, since Metal Substrates asks for near-white metal while citing the commercial grade power tool cleaning standard, has the specifier said which cleanliness governs, and has the ICRI surface profile reference been added to the References article?
Flashing heights, curbs, walls, and terminationsSequencing (permanent flashing and counterflashing in accordance with NRCA CONDET) + Re-Roof Preparation (remove base flashings, counterflashings, and pitch pans; modify curbs, sills, and equipment for clear curb height) + Preparation item g (paint removed to the minimum height shown on the drawings) + Flashing Membrane Application (termination height where possible, at least the potential water level; do not flash over through-wall flashings, weep holes, or overflow scuppers; fleece overlaps in items g and l) + Walls, Curbs and Bases + Section 07 60 00 + parapet, curb, and wall detailsDo the details show the flashing height at each wall and curb, and where existing curbs, sills, or equipment are too low for the clear height Re-Roof Preparation requires, do the drawings show them raised or modified, is the height to which paint is removed actually shown, as Preparation item g assumes, do the details stop the PMMA below existing through-wall flashings, weeps, and overflow scuppers, and since items g and l of Flashing Membrane Application state different minimum fleece overlaps at side laps, which one governs?
Drains, penetrations, hot pipes, and jointsPenetrations and Flashings (penetrations separated and flashed individually, never ganged; drain target and finger flashing into the bowl; new drains include plumbing and connection to the storm sewer; hot pipes above a stated temperature flashed to a cool sleeve; goosenecks for flexible penetrations; expansion joints over filler, tube, backer rod, and bond breaker tape; vehicle impact protection) + Roof Penetrations (protective cement surface at kitchen vents and grease traps) + Moving crack treatments (bond breaker tape; urethane sealant) + mechanical, plumbing, and electrical roof plans + structural expansion jointsDo the trade roof plans show conduits or pipes grouped in one pitch pan or too close to flash individually, and has the trade that owns them been asked to separate them, are new drains on the plumbing drawings with their piping to the storm system, since the Drains paragraph puts that cost on the contractor, are hot pipes identified with their service temperature so a cool sleeve is detailed, are kitchen exhaust and grease discharge points marked for the protective surface, and since the crack and expansion joint treatments call for bond breaker tape and urethane sealant that PART 2 does not specify, are they added or sent to Section 07 92 00?
Traffic areas, wearing layer, continuity testing, and cool roofSystem Components (membrane, resin-mortar wearing layer, surfacing, and finish) + Surfacing and Finish Layer bracket (optional; light or heavy texture) + Waterproof PMMA Mortar Wearing Layer + Waterproofing Continuity Testing (low voltage, high voltage, or flood test before wearing layers) + Traffic Surfacing and Finish (standard duty secondary deck areas, heavy duty main deck areas, full-depth or surface-applied striping, color breaks approved by the Government) + Cool Roofs note and bracket (UFC 3-110-03 and ASHRAE 90.1 Chapter 5; condensation in colder climate zones) + deck and roof plansDo the plans mark which areas are roof only, pedestrian, or vehicular, and which are standard duty secondary deck or heavy duty main deck, with the striping layout and color breaks, since System Components lists the wearing layer and surfacing for every area while the surfacing article is optional, is one continuity test method chosen and confirmed with the manufacturer and the testing agency for this substrate, and is the cool roof bracket kept or deleted to follow the energy analysis and the climate zone, as its note warns?
Field tests, inspections, warranty, and closeoutSubmittals (SD-06 existing conditions report; SD-09 Field Tests and bracketed Manufacturer’s Inspection Report; SD-11 Warranty and Information Card) + Field Quality Control (“Perform field tests” with no test named) + Manufacturer’s Inspection note, Frequency bracket, and Field Inspection Report + Manufacturer’s Warranty (no-dollar-limit system warranty including insulation “[ in compliance with ASTM D5034]”; acceptance by a “Roofing System Engineer of Record”) + Contractor’s Warranty + Information Card (“number of plies”, tapered insulation) + Section 01 45 00Has the specifier named the field tests SD-09 asks for, such as the adhesion and continuity tests the section describes elsewhere, and matched the bracketed Manufacturer’s Inspection Report to the Field Inspection Report its paragraph produces, who is the Roofing System Engineer of Record whose acceptance the warranty waits on, has the bracket tying insulation to ASTM D5034, a textile grab test, been corrected, and has the manufacturer agreed in writing to warrant the existing insulation and membrane the recover leaves in place?

Worked example: a recover over wet insulation, a ganged pitch pan, and an unmarked maintenance deck

Illustrative example: a two-story maintenance hangar office has a granulated modified bitumen roof near the end of its service life and a concrete walkway deck between two roof levels that technicians cross daily. The design team specifies PMMA over the existing roof and the deck to extend their life, and the issued Section 07 18 16 keeps the cover board and wind uplift brackets, the heavy-duty main deck surfacing, and the whole warranty article. The roof plan names no existing system by area, the design documents include no moisture survey, and the roof plan shows no uplift zones or values. The mechanical roof plan places a new exhaust fan on an existing curb lower than the clear curb height the Re-Roof Preparation article requires, and the electrical roof plan routes six conduits through one existing pitch pan. The walkway deck drawings show no traffic areas, striping, or expansion joint detail.

Ask the roof consultant to commission a moisture survey before bidding and to show the wet areas to be removed and their replacement on the roof plan, and to name the existing system of each area. Ask the structural engineer or roof consultant to show the calculated uplift pressures by zone and to confirm that the existing roof can take the cover board attachment. Ask the mechanical engineer to raise the curb and the electrical engineer to separate the conduits so each can be flashed individually, ask the architect to mark the traffic areas, striping, and the expansion joint detail on the walkway deck, and ask the specifier to name the field tests, define the engineer whose acceptance the warranty waits on, and obtain the manufacturer’s written agreement to warrant the existing components left in place.

Avoid a false conflict

Section 07 18 16 covers the PMMA membrane, its flashing membrane, primers, patching, the resin-mortar wearing layer, and traffic surfacing over existing or new roofing. New insulation and recovery board under the membrane follow Section 07 22 00 and the roof insulation guide, counterflashing, cap flashings, and edge metal follow Section 07 60 00 and the flashing and sheet metal guide, wood nailers and blocking follow Section 06 10 00, roof drains and storm piping follow the plumbing section, and the quality control specialist follows Section 01 45 00, so check those before calling a requirement missing. Where PMMA is the membrane under insulation and ballast, Section 07 55 00 Protected Membrane Roofing names Section 07 18 16 as one of its membrane options and governs the layers above it; see the protected membrane roofing guide. EPDM is Section 07 53 23, TPO is 07 54 23, and modified bitumen is 07 52 00, each with its own guide. Its notes cite UFC 3-110-03 Roofing, ASHRAE 90.1 Chapter 5, and ANSI/ASSE A1264.1; confirm the editions your project invokes. Its Product Standards and membrane articles require FM and UL approvals that its References article does not list, its Metal Substrates paragraph pairs near-white metal with the commercial grade power tool cleaning standard, its two flashing paragraphs state different fleece overlaps, its PMMA Detailer Resin appears twice, and its warranty waits on an engineer of record the section does not define. Wind uplift, the structural capacity of the existing roof, fire classification, energy performance, and the warranty are decisions for the roof consultant, the structural engineer, the architect, the manufacturer, and the owner. The current guide section cites ACI 301, ACI SPEC 308.1, ASCE 7-22, SSPC SP 15, ASTM C1325, D41, D570, D1204, D2240, D4541, D5034, D5147, D7264, E96, F2170, and F2659, ISO 9001 and 14001, and NRCA C3701 and CONDET; confirm the editions your project invokes.

When requirements disagree, follow the project’s document-control and clarification process. Do not assume that drawings always override specifications, or the reverse. Identify the exact sources and request an authorized decision.

Close the issue across the affected documents

Record the location or tag, drawing and specification references, issue dates, observed difference, and the decision needed. Assign an owner and keep the item open until the response identifies the governing requirement. Check the revised drawings and specification references together; a response email alone may leave the issued package inconsistent.

For the overall process, use the guide to drawing and specification conflicts. Mark an inapplicable checklist row with a reason, and distinguish a verified correction from a question that still needs design information.

Where Groundbook fits

Groundbook’s drawing and specification review helps investigate potential disagreements in the documents you supply. Include the relevant specification sections and drawing references, then verify the cited evidence with the responsible reviewers before acting on a finding.

Questions, answered

FAQs

What should a PMMA roofing specification review compare?

Compare the existing roof, its moisture survey, and the removals, the cover board, single-ply recover, and wind uplift, the approval listing, fire classification, and qualifications, substrate preparation, moisture, and primers by material, flashing heights, curbs, walls, and terminations, drains, penetrations, hot pipes, and joints, traffic areas, wearing layer, continuity testing, and cool roof, and field tests, inspections, warranty, and closeout.

What should the drawings show for a UFGS 07 18 16 PMMA roof?

The current UFGS 07 18 16 on WBDG has no single drawing note, but its articles rely on the drawings for the minimum height to which wall paint is removed, the overall roof performance unless insulation specified in other sections sets it, and, under its wind uplift note, the calculated uplift values. The review should also look for the existing system of each roof area, the wet areas to be removed, curb and flashing heights, penetrations, drains, expansion joints, and any traffic areas and striping. UFGS numbers are DoD guide specification numbers, not universal MasterFormat titles, and your project’s issued specification governs.

Can PMMA roofing be applied over an existing roof?

The section is written for that use. Its opening note presents PMMA as a way to extend the service life of an existing roof instead of replacing it, over built-up, metal, single-ply, or modified bitumen roofing, provided the existing roof and substrate are structurally sound, properly attached, and dry. Its System Description bracket applies PMMA only after deteriorated and wet membrane and insulation are removed and the roof is accepted, and its Cover Board note warns that some systems need an existing single-ply membrane removed or cut first. The roof consultant and the manufacturer decide whether a given roof qualifies.

How does UFGS 07 18 16 relate to protected membrane roofing?

UFGS 07 55 00 Protected Membrane Roofing names UFGS 07 18 16 as one of the membranes that can sit under its extruded polystyrene insulation, filter fabric, and ballast, and its separation layer note says drainage mats are typically used with liquid-applied systems. In that case Section 07 18 16 governs the membrane and flashings and Section 07 55 00 governs the layers above, the flood test, and the ballast. Check that both sections name the same membrane, since 07 55 00 lists PMMA in only one of its three membrane lists.

Can Groundbook check PMMA roofing drawings against Section 07 18 16?

Groundbook compares the drawing set with the reference documents you upload, such as your issued Section 07 18 16, the roof condition and moisture survey, the mechanical, plumbing, and electrical roof plans, the manufacturer’s details and approval listing, and licensed codes or standards you hold, and links each potential disagreement to both sources. It has no built-in code library and does not perform wind uplift or structural calculations, judge whether an existing roof can be recovered, certify compliance, design the roof, or decide warranty questions. Each finding is a question for the architect, the roof consultant, or the structural engineer.

Keep exploring

Continue your review

Check protected membrane roofing specifications against roof plans, ballast layouts, and drain details

Compare the membrane section, slope, drain openings, ballast design, deck load, insulation, filter fabric, pavers, and flood test with UFGS 07 55 00.

Explore

Check roofing membrane specifications against drawings

Compare TPO roofing membrane scope, substrate, flashing, drainage, and warranty requirements across roof plans and specifications.

Explore

Check EPDM roofing specifications against roof plans and details

Compare EPDM attachment method, ballast and pavers, seam tape, perimeter fastening, flashing, drain sumps, wind zones, and insulation with UFGS 07 53 23.

Explore

Check modified bitumen roofing specifications against roof plans and details

Compare SBS and APP plies, torch limits at wood curbs and nailers, base sheet, flashing, drains, walkpads, and wind and fire listings with UFGS 07 52 00.

Explore

Check roof insulation specifications against roof plans and details

Compare roof insulation R-value, tapered layout, thermal barrier, wind attachment zones, vapor retarder, and nailers with UFGS 07 22 00.

Explore

Check flashing and sheet metal specifications against roof and wall details

Compare sheet metal choices, gutters and downspouts, copings, counterflashing and reglets, expansion joints, and roof edge wind uplift with UFGS 07 60 00.

Explore

Check waterproofing specifications against details

Trace fluid-applied waterproofing from specification to substrates, joints, drains, and terminations. Includes a coordination checklist and editable CSV.

Explore

Check joint sealant specifications against drawings

Compare joint sealant type, joint design, substrate compatibility, and movement capability across wall details and specifications. Editable CSV included.

Explore

UFC 3-110-03 Roofing review of DoD roof plans, details, and specifications

Review DoD roof drawings and specs against the reissued UFC 3-110-03: NRCA and MBMA basis, decks, cover boards, drainage, PV, and recover.

Explore

ASCE 7 design load criteria plan review

Review drawings against ASCE 7: design criteria notes, risk category, wind, snow, and seismic data, and loads for delegated design. With a published finding.

Explore

Roofing and waterproofing review checklist

Trace slope, drainage, overflow, edges, penetrations, and transitions through a roof and below-grade package. 12 prompts and a free editable CSV.

Explore

Senior-living exterior renovation

A senior-living exterior renovation review finds conflicting brick supports, missing insulation requirements and inconsistent waterproofing details.

Explore

Drawings vs. specifications

Compare drawing requirements with specifications, schedules, and controls. Find potential equipment, material, and scope inconsistencies with Groundbook AI.

Explore

Bring your next set into focus

Set up a review or talk through your project with our team.

Check a PMMA roof recover against the roof plan and details

Trusted by hundreds of professionals