Plan check correction · Egress

Plan check correction: exit access travel distance and common path of egress travel

Reviewers ask for travel distances when they cannot see the longest path to an exit on the plans. Common path comments follow when a room or suite reaches one route for too long before a second route opens up.

The comment asks you to draw and dimension the longest path from the most remote point to an exit, and the distance a person travels before two separate routes are available, then compare both with the limits for the occupancy and sprinkler status. Clear it with dimensioned travel paths on the egress plan and a note citing the limits used.

Read the comment

What the plans examiner is asking for

The most remote point

Travel measured from the most remote point of each space along the natural path around walls, furniture, and equipment, not a straight line.

Exit access travel distance

Distance to the nearest exit compared with IBC Section 1017 and Table 1017.2 for the occupancy and sprinkler status.

Common path of egress travel

Distance before two separate routes are available, compared with IBC Section 1006.2.1 and its table.

The limits used

A note naming the limit applied and why, such as the occupancy and whether the building is sprinklered.

Published correction lists

How city lists word this correction

Published lists ask for the exit access travel distance, the common path of egress travel, or dimensioned exit paths. Paraphrased from each department’s own published list; the lists do not rank items by how often they are issued.

Travel distance and common path: published correction list items by citySwipe or scroll sideways to read all columns.
CityWhat the published list asks forCode citedWhere it appears
Los AngelesDimension the common path of egress travel from each space, and add a legend showing exit locations and travel distance from the most remote point on each story.CBC 1006.2.1; CBC T1017.2Commercial Plan Check Correction Sheets (2026 LABC), Part II, H. Means of Egress, items 13 and 40
San FranciscoDocument exit access travel distance from the most remote point and common path of travel where applicable, measured at right angles unless walls guide travel.SFBC 106A.3.4.2.1, item 3dSFBC 106A.3.4.2.1 Contents of site permit application, item 3d
San FranciscoAn existing non-sprinklered R-3 up to three stories may keep one exit and no sprinklers if travel distance, including from decks, stays within 125 feet.SFBC 903.2.8 Exception 5Information Sheet EG-03, Discussion
San DiegoProvide an egress plan for every floor tracing exit travel from the most remote occupied point to a public way, showing travel distance and common path of travel.Project Submittal Manual Section 2, checklist item 5.7.3 (Means of Egress Floor Plans)
New York CityFloor plans must show maximum travel distances, including dead ends and common path of egress.Plan Examination Guidelines – Section 2.4.1 Floor Plans (Egress)

Sources reviewed September 12, 2026. Code sections are as cited on each list and follow that city’s adopted code. Confirm the current list and edition with the department.

Revise the set

What changes on the drawings, and what else to re-check

Fixing a long travel path often means a new door or exit, which reaches well beyond the egress plan.

Travel distance and common path: sheets to revise and dependent sheetsSwipe or scroll sideways to read all columns.
ChangeSheets to reviseAlso re-check
Second exit access door addedFloor plan; egress plan; door scheduleExit separation distance, hardware, accessible route to the new door, rated corridor openings
Partition layout revisedFloor plan; enlarged plansReflected ceiling plan, sprinkler layout, electrical devices on relocated walls
Sprinkler basis relied onCode analysis; fire protection notesDeferred sprinkler submittal, corridor rating reductions that depend on sprinklers
Exit stair relocatedFloor plans on every level; stair sectionsStructural openings, shaft ratings, discharge path at grade

Close the comment

A response the reviewer can verify

An illustrative example written for this guide, not a real project or a city’s wording. Name the sheet, the detail, and the change, so the recheck does not start with a search.

Comment

Show common path of egress travel and exit access travel distance for the suite. Travel distance appears to exceed the allowable.

Response

Revised as requested. Travel paths are dimensioned on A0.11 from the most remote points. A second exit access door (Door 212) has been added to the suite, reducing common path to 68 feet. Longest exit access travel distance is 187 feet, within the limit for a sprinklered Group B occupancy.

How to write the whole response letter

Before you submit

Catch it before the plans examiner does

  1. Find the most remote points

    Mark the corners of each space farthest from its exits, including rooms behind other rooms.

  2. Draw the real path

    Follow corridors, doors, and fixed furniture. Straight-line dimensions invite a correction.

  3. Check the dependencies

    If the result relies on sprinklers, make sure the code analysis and fire protection notes say the building is sprinklered.

Groundbook compares the drawings, schedules, and specifications with the code and local references you upload, and links each potential issue to the sheets and sections behind it. Your team verifies each finding; the jurisdiction makes every approval decision. See the pre-permit review and drawing-to-code review.

Questions, answered

Travel distance and common path: questions

What is the difference between travel distance and common path?

Exit access travel distance runs from the most remote point to the nearest exit. Common path of egress travel is only the first part, before occupants have a choice of two separate routes.

Is travel distance measured inside exit stairs?

No. Exit access travel distance ends at the entrance to an exit, such as an exit stair enclosure or an exterior exit door. Travel inside the exit is not counted.

Do sprinklers increase the allowable distance?

Usually. The limits in IBC Table 1017.2 and the common path table are higher for many occupancies when the building has an automatic sprinkler system.

Find the corrections before the plans examiner does

Upload the drawing set with the code and local references that govern it. Groundbook links each potential issue to its sources for your team to verify.