| Code analysis | The first sheet needs a data table giving construction type and occupancy classifications (existing and proposed), number of stories, and the building code edition used for design. | — | Title/cover sheet | Project Submittal Manual Section 2, Minimum Submittal Requirements Checklist, item 3.1 (Title Sheet) |
| Occupant load and egress width | Label every space with its use and occupant load, derived from CBC occupant load factors and the City's technical bulletin on occupant load. | Technical Bulletin BLDG-10-1 | Egress plans, floor plans | Project Submittal Manual Section 2, checklist item 5.7.1 (Space and Occupant Loads) |
| Travel distance and common path | Provide an egress plan for every floor tracing exit travel from the most remote occupied point to a public way, showing travel distance and common path of travel. | — | Egress plans | Project Submittal Manual Section 2, checklist item 5.7.3 (Means of Egress Floor Plans) |
| Number and separation of exits | Egress plans must identify exit access, exits and exit discharge, and state exits required versus provided; rated corridors, horizontal exits and stair enclosures must be labeled. | — | Egress plans, floor plans | Project Submittal Manual Section 2, checklist items 5.7.2 and 5.7.3 |
| Stairs, handrails, and guards | Include dimensioned details of all stairs, handrails and guardrails, and show each stairway's location and travel direction on floor plans. | — | Architectural details, floor plans, building sections | Project Submittal Manual Section 2, checklist items 5.6.1 and 5.1.8 |
| Fire-rated assemblies | Where fire-resistive construction is proposed, show rated shafts, fire walls, fire barriers, fire partitions, rated corridors and horizontal exits on the floor plans. | — | Floor plans, life safety plans | Project Submittal Manual Section 2, checklist item 5.1.10 (Fire Resistive Construction) |
| Rated openings and penetrations | Detail rated walls, ceilings, floors, roofs, shafts and penetrations, citing each assembly's listing number (such as UL or ICC); door schedules should list fire ratings. | — | Architectural details, door and window schedules | Project Submittal Manual Section 2, checklist items 5.6.2 and 5.5.1 |
| Fire separation distance | The site plan must dimension fire separation distance between adjoining buildings and from property lines to every building or structure. | — | Site plan | Project Submittal Manual Section 2, checklist item 4.1.10 (Fire Separation Distances) |
| Accessible toilet rooms | Provide fully dimensioned enlarged plans and interior elevations of kitchens, powder rooms and all bathrooms demonstrating accessibility compliance. | CBC Chapter 11A and 11B | Enlarged plans, interior elevations | Project Submittal Manual Section 2, checklist item 5.1.7 (Accessibility - Enlarged Floor Plans and Interior Elevations) |
| Path of travel in alterations | Inside the building, floor plans must trace the accessible route to all rooms and to path-of-travel elements such as toilet rooms, drinking fountains and public telephones. | CBC Chapter 11A and/or 11B | Floor plans, accessibility plans | Project Submittal Manual Section 2, checklist Accessibility Plans, Path of Travel item (numbered 4.2.5 in the source) |
| Special inspection | Structural sheets must include a statement of special inspections listing work that needs special inspection and testing, with related notes. | CBC Chapter 17 | Structural general notes | Project Submittal Manual Section 2, checklist item 6.1.5; Technical Bulletin BLDG-17-2 |
| Deferred submittals | The architect or engineer of record must list deferred items on the construction documents; only components in the bulletin's Table 1 are deferrable without building official approval. | — | Title/cover sheet | Information Bulletin 188, Deferred Submittals (Table 1 and listing requirement) |
| Deferred submittals | If prefabricated trusses are deferred, permit plans still need a truss layout, shear transfer details compatible with the trusses, and a summary of truss design loads. | — | Roof/floor framing plans, structural details | Project Submittal Manual Section 2, checklist items 12.0-12.3 (Truss Plans and Calculations) |
| Sheet coordination | Every detail used in structural calculations must appear on the plans and be cross-referenced to roof, floor or foundation plans; architectural grid lines should match structural grid lines. | — | Structural plans and details, architectural floor plans | Project Submittal Manual Section 2, checklist items 11.3 and 5.1.11 |
| Allowable height and area | Recommended floor area analysis per the CBC: tabulate square footage by occupancy against the allowable area for that occupancy and construction type. | — | Title sheet or code analysis sheet | Project Submittal Manual Section 2, checklist item 3.8 (Floor Area Analysis Calculation) |
| Allowable height and area | If open yards are used to increase allowable area (frontage increase), show the extent and depth of those yards on the site plan. | — | Site plan | Project Submittal Manual Section 2, checklist item 4.1.18 (Allowable Area Frontage Increase) |
| Accessible route and entrances | Show at least one accessible route from accessible parking, loading zones, public sidewalks and transit stops to the entrance served, and show exterior entrances meeting accessibility requirements. | CBC Chapter 11A and/or 11B | Site plan, accessibility plans | Project Submittal Manual Section 2, checklist items 4.2.1, 4.2.3 and 4.2.5 (Accessibility Plans) |
| Structural calculations and signatures | Plans need a California architect or engineer in responsible charge. Plans may be unsigned at submittal but signed before issuance; calculations must be stamped and signed at submittal. | Business and Professions Code 5535-5538 | Title sheet, all sealed sheets, calculation cover | Project Submittal Manual Section 2, checklist items 3.5 (Responsible Charge) and 11.1 |
| Geotechnical report | Provide a site-specific, stamped geotechnical report when the municipal code requires it; reports over three years old need an update letter, and foundations must follow its recommendations. | SDMC 145.1803, Table 145.1803 | Foundation plans, structural notes | Project Submittal Manual Section 2, checklist items 13.0-13.3 and 6.2.1 |
| Energy compliance | For non-residential, high-rise residential and hotel projects, envelope, mechanical and indoor/outdoor lighting Title 24 forms must appear on the plans, signed by a licensed design professional. | NRCC compliance forms (California Energy Code) | Title 24 (T) sheets; window schedule U-factor/SHGC | Project Submittal Manual Section 2, checklist items 10.0-10.1 and 5.5.1 |
| Green building | Include notes and details demonstrating compliance with the California Green Building Standards Code. | California Green Building Standards Code | General notes / CALGreen sheet | Project Submittal Manual Section 2, checklist item 3.10 (Cal Green Standards) |
| Plumbing fixture count | Show existing, proposed and relocated plumbing fixtures (and, for non-residential work, fixtures being removed); a Water Meter Data Card must list new and existing fixtures. | Form DS-16 | Floor plans, plumbing plans | Project Submittal Manual Section 2, checklist items 5.1.5 and 1.2 |
| Fire sprinklers and alarms | Fire alarm and sprinkler plans may be deferred, yet life safety review of building plans proceeds; alarm devices drawn on electrical sheets are not reviewed and need a separate package. | Information Bulletins 137 and 139 | Fire protection (F) sheets, electrical plans | Project Submittal Manual Section 2, checklist items 8.0, 15.0 and 16.0 |
| Site plan information | The site plan must show dimensioned property lines, setbacks, easements by type, right-of-way work, and existing and proposed structures with distances; surveyed lines and easements need a land surveyor's seal. | — | Site plan | Project Submittal Manual Section 2, checklist items 4.1.1-4.1.7; Information Bulletin 122 |
| Other | Each sheet needs a unique discipline-letter number at bottom right, in Arial or Helvetica with no lowercase or special characters; one page size and orientation throughout. | — | All sheets (title block) | Requirements for Digital Plans & Documents (Sheet Numbering, Page Size, Page Orientation) |