| Code analysis | The architectural sheet must carry a complete IBC/DBC code analysis covering, at minimum, scope of work, construction type, building height, number of stories, occupancy classification, the chosen energy code compliance method, fire sprinkler/alarm/detection status, occupant loads, the egress plan, and gross building areas. | — | cover sheet / code analysis on architectural plan | Commercial Building Permit Guide, Applications and Submittal Requirements checklist |
| Occupant load and egress width | Denver's local occupant-load table departs from the base code for several space types: it revises the factor for 'business areas' to require using whichever of the gross or net method yields the higher load, and adds Denver-specific factors for pool decks and for marijuana plant-husbandry flowering/vegetative and CO2-enriched work rooms. | DBC Table 1004.5 | occupant load / code analysis sheet | 2025 Denver Building Code, Chapter 10: Means of Egress, Section 1004 Occupant Load |
| Travel distance and common path | For the single-exit Group R-2 option, Denver's local table caps exit-access travel distance at 125 feet for basement through fourth-story (or third-story-plus-occupiable-roof) buildings, and does not permit the single-exit path at all on the fifth story or higher. | DBC Table 1006.3.4(1) | egress/life-safety plan | 2025 Denver Building Code, Chapter 10: Means of Egress, Section 1006, Table 1006.3.4(1) |
| Number and separation of exits | Denver added a local 'single-stair' exception letting Group R-2 buildings up to five stories above grade (four with an occupiable roof) use one exit if a lengthy list of conditions is met together: no more than four dwelling units per story, gross floor area capped per story, a citywide fire sprinkler system, one-hour-rated corridors, 2-hour-rated exit stairway/elevator shaft enclosures, minimum stair widths of 48 or 54 inches depending on floor area, dedicated emergency escape openings, and a posted 'this building contains only one stair' sign at the fire alarm panel. | DBC 1006.3.4, item 6 and subparts 6.1-6.19 | egress/life-safety plan; code analysis | 2025 Denver Building Code, Chapter 10: Means of Egress, Section 1006 Number of Exits and Exit Access Doorways |
| Stairs, handrails, and guards | Stair drawings and details must show and dimension stair width, headroom, riser/tread dimensions, overall vertical rise, landings, and handrails. | DRC R318.7.1-R318.7.8 | details/enlarged stair drawings | Permitting Checklist for New Homes and Additions, Details/Enlarged Drawings table, Stairs row |
| Stairs, handrails, and guards | Denver added a local requirement that interior exit stairways and ramps running to the top story of buildings four or more stories above grade have a roof hatch openable to the exterior, at least 16 square feet in area with a 2-foot minimum dimension, with narrow exceptions for pressurized enclosures, penthouse-protected enclosures, and steep roof slopes. | DBC 1011.12.3 | roof plan; stair sections | 2025 Denver Building Code, Chapter 10: Means of Egress, Section 1011 Stairways |
| Fire-rated assemblies | Fire-rated walls and projections must be labeled with their rating and backed by a UL listing number, an ICC-ES report, or a prescriptive assembly identified from the local fire-resistance section; drawings must also label the fire separation between garage and dwelling unit and between dwelling units, gypsum protection at under-stair spaces, and floor-assembly fire protection. | DRC R302; DCBC Section 721 | floor plans; wall sections; details | Permitting Checklist for New Homes and Additions, Floor Plans/Reflected Ceiling Plans table, Fire Rated Walls and Separations row |
| Fire-rated assemblies | Denver added local exceptions removing the fire-resistive construction requirement for corridor walls and ceilings inside single-tenant office spaces, and for corridors serving a conference or assembly room with an occupant load under 100 within a single-tenant office space. | DBC 1020.2, Exceptions 6-7 | fire/life-safety plan; corridor wall type legend | 2025 Denver Building Code, Chapter 10: Means of Egress, Section 1020 Corridors |
| Rated openings and penetrations | The percentage of unprotected and protected openings allowed in an exterior wall is set per story by the local fire-separation-distance table, measured from the building face within the height of that story closest to the line used to determine fire separation distance, and applies to openings with or without windows as well as duct and air-transfer openings. | DBC 705.9.1; DBC Table 705.9 | exterior elevations; opening area table | 2025 Denver Building Code, Chapter 7: Fire and Smoke Protection Features, Section 705 Exterior Walls |
| Fire separation distance | Roof overhangs must be dimensioned along with their distance to the property line; where an overhang sits within 5 feet of the property line, the drawings must note or detail its fire-resistance rating. | DRC R302.1 | exterior elevations; roof plan | Permitting Checklist for New Homes and Additions, Exterior Elevations table, Overhang Dimensions row |
| Special inspection | Plans must include a statement of required special inspections and a list of structural observations required by the engineer or building official; if loads added to an existing structure increase by more than 5%, a signed and sealed letter from a licensed engineer stating a personal inspection was performed and the structure is adequate must also be provided. | DCBC 1704-1705; DCBC 1704.6; DCBC 133.2.2 | structural general notes | Permitting Checklist for New Homes and Additions, Structural Documents table, Special Inspections/Structural Observations/Letter of Integrity rows |
| Deferred submittals | Every item to be deferred (typically specialty engineering such as precast concrete, trusses, shop-fabricated stairs or fire alarm systems) must be listed together in the project's initial code analysis and referenced on the relevant discipline sheets; each deferred item still needs its own permit and inspection before a certificate of occupancy will issue. | — | code analysis; architectural/engineering discipline sheets | Commercial Building Permit Guide, Deferred and Phased Construction section |
| Sheet coordination | Every drawing must use a common graphic or engineering/architectural scale, include a north arrow, provide a graphic legend or key for all line types, symbols and abbreviations used, and include callouts/tags for all physical elements and dimensions shown. | DCBC 133.2 | all drawing sheets | Permitting Checklist for New Homes and Additions, Requirements for All Project Submittals table, Plan Graphics row |
| Allowable height and area | Denver's 2025 amendment to the building-area formula changes how the tabular allowable-area factor is pulled for single-occupancy buildings: the amended section directs use of the applicable NS/S1/S13R/S13D/SM value straight from the local Table 506.2 in the area equation. | DBC 506.2.1 | code analysis / allowable area calculations | 2025 Denver Building Code, Chapter 5: General Building Heights and Areas, Section 506 Building Area |
| Accessible route and entrances | Denver rewrote the accessible-EV-charging-space count so that at least 5 percent (minimum one) of vehicle spaces served by EV charging equipment must be accessible, and added a further requirement that remaining EVSE spaces be built as 'universal' vehicle charging spaces at 132 inches wide with a 60-inch access aisle, following ICC A117.1 reach-range and equipment provisions. | DBC 1107.2.1; DBC 1107.2.3 | site/parking plan; accessibility details | 2025 Denver Building Code, Chapter 11: Accessibility, Section 1107 Motor-Vehicle-Related Facilities |
| Accessible route and entrances | Two-way emergency communication call boxes on accessible means of egress must have an ANSI A117.1-compliant protective cover operable with one hand within a 5-lb force limit, plus specific posted and Braille signage (identifying the floor, giving push-button instructions, and directing occupants to wait for assistance) at each call box location. | DBC 1009.8.1; DBC 1009.8.2 | life-safety plan; stair enclosure details/signage schedule | 2025 Denver Building Code, Chapter 10: Means of Egress, Section 1009 Accessible Means of Egress |
| Structural calculations and signatures | Structural general notes must list live, dead, snow and wind loads, seismic design category, and soil parameters (from the soils report, or IRC Table R401.4.1 prescriptive values where no report is required); for ASCE 7-22 sites the notes must distinguish the strength-level ground snow load (Pg) used for engineered designs from the Pg(ASD) value used with IRC prescriptive tables. | DRC Table R301.2; DCBC Chapter 16 | structural general notes | Permitting Checklist for New Homes and Additions, Structural Documents table, Load Information row |
| Structural calculations and signatures | Denver added a local live-load provision for structural decks that fire apparatus can access: the deck must be designed for the greater of the standard trucking load, an existing fire-access load section, or specific platform-truck/ladder-truck axle and outrigger load cases defined by Denver Fire Department vehicle geometry, and the completed deck must be posted with permanent load-rating signage at each entrance. | DBC 1607.8.2 | structural general notes; foundation/deck framing plan | 2025 Denver Building Code, Chapter 16: Structural Design, Section 1607 Live Loads |
| Geotechnical report | A current geotechnical soils report is required for new dwellings/townhouses/conditioned accessory structures, for excavation/benching/sloping/shoring work covered by the excavation policy, for additions using a deep foundation or built over prior excavation areas, and wherever expansive, compressible or shifting soils are likely. | DRC R401.4; Building Code Policy (Excavation, Sloping, Benching, and Shoring for DRC Structures) | foundation plan; structural general notes | Permitting Checklist for New Homes and Additions, Survey & Geotechnical Soils Report table |
| Energy compliance | Commercial submittals must include an Energy Compliance Package: a complete energy checklist, all applicable COMcheck forms, and an energy model submittal, each stamped and signed as required. | — | energy compliance sheets | Commercial Building Permit Guide, Applications and Submittal Requirements checklist |
| Energy compliance | Residential projects must submit a completed Denver Energy Code Residential Checklist for new construction and for additions/alterations expanding above-grade area by 20% or 300 sq ft (whichever is less); a new HVAC system additionally needs ACCA Manual J/S/D packages, and the compliance report required (none, RESCheck, a third-party energy model, or an ERI rating report) depends on the chosen compliance pathway. | DEC R103.2; DEC R403.7; DEC R402.1.5; DEC R405.3.2; DEC R406 | energy compliance sheets; mechanical plans | Permitting Checklist for New Homes and Additions, Energy Documents table |
| Green building | New buildings, additions, and qualifying roof permits at or above 25,000 sq ft of gross floor area must comply with the mandatory Green Buildings Ordinance: install a 'cool roof' and choose one flexible compliance option (green roof/ground green space, renewable energy, greater energy efficiency, LEED or similar certification, an innovative energy program for existing buildings, or funding off-site green space), and submit a signed Green Building Declaration Form. | — | green building declaration/checklist sheets | Commercial Building Permit Guide, Green Building Ordinance section |
| Green building | A signed Denver Green Code Limited Mandatory Use Checklist is a required submittal item separate from the Green Buildings Ordinance declaration. | — | green code checklist sheet | Commercial Building Permit Guide, Applications and Submittal Requirements checklist |
| Plumbing fixture count | Where an all-gender multi-user toilet room is provided, Denver requires each water closet in its own floor-to-ceiling compartment with no sightlines and a lockable door; a urinal may be included only inside a compartment, and such a urinal does not count toward the building's required plumbing fixture count. | DBC 2902.8 | restroom enlarged plans; plumbing fixture count table | 2025 Denver Building Code, Chapter 29: Plumbing Systems, Section 2902 Minimum Plumbing Facilities |
| Plumbing fixture count | Denver added a fixture-count rule specific to drive-in restaurants and drive-in movie theaters: public toilet facilities must be sized to an occupant load equal to twice the number of parking stalls provided, in addition to fixtures otherwise required. | DBC 2902.10 | plumbing fixture count table; site plan (parking stall count) | 2025 Denver Building Code, Chapter 29: Plumbing Systems, Section 2902 Minimum Plumbing Facilities |
| Fire sprinklers and alarms | Denver requires an automatic fire sprinkler system in one- and two-family dwellings, townhouse units, live/work units, and care facilities wherever a habitable attic is built above the third story (plus additional triggers for townhouse family child care and live/work and care uses); required systems must be designed to NFPA 13D or 13R with demand satisfied by Denver Water's site pressure without a fire pump. | DRC R309.1-R309.4 | structural/architectural general notes; fire protection notes | 2025 Denver Building Code (Residential), Section R309 Automatic Fire Sprinkler Systems |
| Site plan information | The site plan must show and dimension zone lot lines labeled by street/side/rear designation, all abutting streets and alleys (with alley width and public/private status), every existing and proposed structure with dimensions, driveways, sidewalks (including one from the street to the building entry), and site stairs with spot elevations at landings. | DCBC 133.2; DCBC 133.2.2; DZC 13.1.5.2; DZC 13.1.5.16; DZC 13.1.6.3.B | site plan | Permitting Checklist for New Homes and Additions, Site Plan table |
| Site plan information | When a proposed exterior wall sits less than 3 feet from the required zone-district setback (or Former Chapter 59 building separation), the drawings must add setback-verification dimensions from the property/zone lot line to the outside face of the foundation wall, exterior wall, and roof overhangs (fascia). | DCBC 133.3 | site plan; exterior elevations | Permitting Checklist for New Homes and Additions, Site Plan and Exterior Elevations tables (Setback Verification row) |