Plan check correction · Egress

Plan check correction: stair, handrail, and guard details

Stair comments are among the most specific a reviewer writes, because every value can be checked against a number. A section without dimensions, or a guard detail without a height, gets a correction.

The comment asks for stair sections and details dimensioned well enough to verify riser height, tread depth, headroom, width, handrail height and extensions, and guard height and openings. Clear it with a dimensioned stair section, enlarged handrail and guard details, and a note on the design loads the guard is built for.

Read the comment

What the plans examiner is asking for

Riser and tread

Riser height and tread depth on the section, compared with IBC Section 1011.5.2: 7 inches maximum riser and 11 inches minimum tread for most commercial stairs.

Headroom and width

Minimum headroom of 80 inches measured from the nosing line, and the stair width required by the occupant load.

Handrails

Height between 34 and 38 inches, graspability, continuity, and extensions at the top and bottom under IBC Section 1014.

Guards

Guard height of 42 inches in most occupancies, and openings that stop a 4-inch sphere up to 36 inches high and a 4-3/8-inch sphere above that, under IBC Section 1015, plus the structural loads in Chapter 16.

Published correction lists

How city lists word this correction

Published lists ask for stair sections, handrail details, guard details, or specific dimensions such as riser height and headroom. Paraphrased from each department’s own published list; the lists do not rank items by how often they are issued.

Stairs, handrails, and guards: published correction list items by citySwipe or scroll sideways to read all columns.
CityWhat the published list asks forCode citedWhere it appears
Los AngelesDetail every stairway: 7 in. maximum riser, 11 in. minimum tread, 6 ft 8 in. headroom, required width, landings, handrail height, grip size and extensions, and 42 in. guards.CBC 1011.2, 1011.3, 1011.5, 1011.6, 1014.2, 1014.4, 1014.7, 1015.3Commercial Plan Check Correction Sheets (2026 LABC), Part II, H. Means of Egress, item 25
San DiegoInclude dimensioned details of all stairs, handrails and guardrails, and show each stairway's location and travel direction on floor plans.Project Submittal Manual Section 2, checklist items 5.6.1 and 5.1.8
SeattleStair plans and sections show landing size, rise and run, headroom, handrail grip, extensions and returns, guard height and intermediate rail spacing, and protection under enclosed stairs.Screening Standards - NEW Commercial Projects, Stair Information and Stair Section
New York CityInclude stair plans and stair sections with handrail and guard details, including guards at balconies and atriums.Plan Examination Guidelines – Sections 2.4.1 (Egress) and 2.4.3 Building Sections

Sources reviewed September 12, 2026. Code sections are as cited on each list and follow that city’s adopted code. Confirm the current list and edition with the department.

Revise the set

What changes on the drawings, and what else to re-check

Stair geometry is tied to floor-to-floor heights and structure, so small changes can move landings.

Stairs, handrails, and guards: sheets to revise and dependent sheetsSwipe or scroll sideways to read all columns.
ChangeSheets to reviseAlso re-check
Riser count changedStair plans and sectionsFloor-to-floor heights on building sections, landing lengths, structural stringers
Handrail extension addedStair plans; handrail detailClear width at landings, door swings into the stair, wall blocking
Guard height or infill changedGuard detail; stair sectionStructural attachment, specification section for metal railings, delegated design notes
Headroom correctedStair sectionBeam and duct locations above the stair on structural and mechanical sheets

Close the comment

A response the reviewer can verify

An illustrative example written for this guide, not a real project or a city’s wording. Name the sheet, the detail, and the change, so the recheck does not start with a search.

Comment

Provide a dimensioned stair section and guard details. Show riser, tread, headroom, handrail height and extensions, and guard openings.

Response

Revised as requested. Stair 1 section on A5.01 shows 17 risers at 6.94 inches, 11-inch treads, and 7 feet 2 inches minimum headroom. Handrail detail 3/A5.02 shows 36-inch height and 12-inch top extension. Guard detail 4/A5.02 shows 42-inch height and 3.5-inch picket spacing; guard load notes added.

How to write the whole response letter

Before you submit

Catch it before the plans examiner does

  1. Dimension the section

    Show risers, treads, headroom, and landing lengths on the stair section itself, not only in notes.

  2. Detail every rail

    Draw handrail and guard details with heights, extensions, and opening sizes.

  3. Check what is above

    Look at structural and mechanical sheets for beams and ducts that reduce headroom.

Groundbook compares the drawings, schedules, and specifications with the code and local references you upload, and links each potential issue to the sheets and sections behind it. Your team verifies each finding; the jurisdiction makes every approval decision. See the pre-permit review and drawing-to-code review.

Questions, answered

Stairs, handrails, and guards: questions

What riser and tread dimensions do most commercial stairs need?

Under IBC Section 1011.5.2, risers are between 4 and 7 inches and treads at least 11 inches. Dwelling units and some other stairs have different limits; check the adopted code.

Is a guard the same as a handrail?

No. A handrail is something to hold while using the stair. A guard prevents falls from an open side. A stair can need both, and each has its own height and details.

Do reviewers need guard load calculations?

Many departments ask for the design loads on the drawings and calculations or a deferred submittal when the guard is delegated to a fabricator. Check the correction wording.