Plan check correction · Egress

Plan check correction: number of exits and exit separation

A space or story that needs two exits but shows one, or two exits placed side by side, draws a correction that can move doors, corridors, and stairs.

The comment asks you to show that each room, space, and story has the number of exits its occupant load and travel distances require, and that the exits are far enough apart. Clear it by showing the required number with its basis, and dimensioning the separation against the overall diagonal of the area served.

Read the comment

What the plans examiner is asking for

Exits required per space

Rooms and spaces that exceed the single-exit occupant load or common path limits in IBC Table 1006.2.1 need two exit access doorways, and more above 500 occupants.

Exits required per story

The number of exits for each story based on its occupant load, under IBC Section 1006.3.3 and Table 1006.3.3.

Separation dimension

Where two exits are required, the distance between them measured against the overall diagonal of the area served: one half, or one third in sprinklered buildings, under IBC Section 1007.1.1.

Independence of routes

Evidence that the paths to the two exits do not pass through the same point or the same room.

Published correction lists

How city lists word this correction

Published lists ask for the number of exits, the exit separation dimension, or a second means of egress. Paraphrased from each department’s own published list; the lists do not rank items by how often they are issued.

Number and separation of exits: published correction list items by citySwipe or scroll sideways to read all columns.
CityWhat the published list asks forCode citedWhere it appears
Los AngelesProvide two exits from any space or story whose occupant load exceeds the table limit, for example more than 49 occupants in Groups A, B, E, F, M or U.CBC T1006.2.1Commercial Plan Check Correction Sheets (2026 LABC), Part II, H. Means of Egress, item 12
San FranciscoAt site permit, DBI checks that the proposed egress system provides enough exits and identifies major potential egress requirements.Site Permit Review Criteria memo - Means of Egress
San DiegoEgress plans must identify exit access, exits and exit discharge, and state exits required versus provided; rated corridors, horizontal exits and stair enclosures must be labeled.Project Submittal Manual Section 2, checklist items 5.7.2 and 5.7.3
SeattleEgress plans should show and dimension the separation between exits, and identify building exits, horizontal exits, refuge areas, and exit passageways or enclosures.Screening Standards - NEW Commercial Projects, Means of Egress/Exiting Plan
New York CityThe NDR floor plan checklist asks for the number of exits on each floor and two means of egress, with accessibility on the first floor.Plan Exam Guidelines for Next Day Review – item A.09 Egress Calculations

Sources reviewed September 12, 2026. Code sections are as cited on each list and follow that city’s adopted code. Confirm the current list and edition with the department.

Revise the set

What changes on the drawings, and what else to re-check

Adding or moving an exit is one of the largest changes a correction can force, so check the whole chain.

Number and separation of exits: sheets to revise and dependent sheetsSwipe or scroll sideways to read all columns.
ChangeSheets to reviseAlso re-check
Second door added to a roomFloor plan; door scheduleSwing direction, hardware, accessible clearances, corridor rating at the new opening
Exit relocated for separationFloor plans; egress plan with diagonalTravel distances, exit discharge, site plan path to the public way
Second stair addedFloor plans on every level; stair sections; roof planStructural framing, shaft enclosures, fire department access, elevator lobby layout
Diagonal re-measuredEgress planCode analysis note on sprinkler status that the one-third rule depends on

Close the comment

A response the reviewer can verify

An illustrative example written for this guide, not a real project or a city’s wording. Name the sheet, the detail, and the change, so the recheck does not start with a search.

Comment

Two exits are required from the second floor. Show exit separation of not less than one-third of the overall diagonal.

Response

Revised as requested. Egress plan A0.12 shows the overall diagonal of the second floor (212 feet) and the distance between exit stairs 1 and 2 (84 feet), greater than one-third of the diagonal for this sprinklered building. Stair 2 relocated to the east end; structural plan S2.02 updated.

How to write the whole response letter

Before you submit

Catch it before the plans examiner does

  1. Check thresholds early

    Compare each space’s occupant load and common path with the single-exit limits before the plan is fixed.

  2. Draw the diagonal

    Show the overall diagonal and the separation dimension on the egress plan.

  3. Follow the routes

    Trace both exit paths and confirm they do not converge before reaching separate exits.

Groundbook compares the drawings, schedules, and specifications with the code and local references you upload, and links each potential issue to the sheets and sections behind it. Your team verifies each finding; the jurisdiction makes every approval decision. See the pre-permit review and drawing-to-code review.

Questions, answered

Number and separation of exits: questions

How is exit separation measured?

Measure the straight-line distance between the exits or exit access doorways and compare it with the maximum overall diagonal of the building or area they serve.

Can a building have a single exit?

Some small stories can, within the occupant load and travel distance limits of IBC Section 1006.3.4 and its tables. The plans should state which provision is used.

Do scissor stairs count as two exits?

No. Under IBC Section 1007.1.1, interlocking or scissor stairways count as one exit stairway. A second required exit needs its own separated stair or route.